Structure & Egress Inputs

Required Egress Schedule

2021 International Fire Code (IFC) | IFC 2021 Table 3103.12.2
PERMIT TRIGGERED
Required Exit Count 3 exits 267 governing occupants
Min Width per Exit 72" Tent clear opening
Aggregate Exit Width 216" 0.2" / person factor
Room Diagonal 107.7 ft 40' x 100' footprint
Min Exit Separation 53.9 ft 1/2 diagonal (IFC 1007.1.1)
Max Travel Distance 100 ft IFC 3103.11 tent limit
Illuminated Exit Signs Required Battery backup at 50+ occ
50% Main Exit Rule Not triggered Indoor assembly > 300 occ
Deterministic Code Basis
Diagonal D = sqrt(40^2 + 100^2) = 107.7 ft | Min Remote Separation = 1/2 diagonal x 107.7 = 53.9 ft
Aggregate Width = max(267 x 0.2" = 54", 3 x 72" = 216") = 216" clear
SCALED EGRESS & DIAGONAL SEPARATION DIAGRAM 40'-0" x 100'-0" (4,000 SQ FT)
DIAG 107.7 ftMIN SEP >= 53.9 ft40'-0"100'-0"EX-1 (72")EX-2EX-3
Open in EgressCAD Studio (40x100 ft)

IFC Table 3103.11 Exit Count & Minimum Width Reference

Active occupant load bracket is highlighted. Tent minimums reflect IFC Table 3103.11 (Table 3103.12.2 in 2018/2021 IFC); indoor minimums reflect IFC Section 1006.2.1 and 1006.3.3.

Occupant LoadTent Min ExitsTent Min Width EachTent Min AggregateIndoor Min ExitsIndoor Min Door Width
10 to 199272" (6 ft)144"236"
200 to 499372" (6 ft)216"236"
500 to 999496" (8 ft)384"336"
1,000 to 1,9995120" (10 ft)600"436"
2,000 to 2,9996120" (10 ft)720"436"
3,000 or more7120" (10 ft)840"436"

Save Plan & Permit Rule Updates

Copy a read-only review link to share with venues or clients now, or save your email for local AHJ permit rule updates.

Frequently Asked Questions

How many exits does an event tent require under IFC Table 3103.11?

IFC Table 3103.11 (Table 3103.12.2 in IFC 2018 and 2021) requires 2 exits of at least 72 inches each for 10 to 199 occupants, 3 exits of 72 inches for 200 to 499 occupants, 4 exits of 96 inches for 500 to 999 occupants, 5 exits of 120 inches for 1,000 to 1,999 occupants, 6 exits for 2,000 to 2,999, and 7 exits for 3,000 or more occupants.

What is the IFC Section 1007.1.1 half-diagonal remote exit rule?

When two or more exits are required, at least two exits must be placed a distance apart equal to not less than one-half (1/2) of the length of the maximum overall diagonal dimension of the room or tent. In fully sprinklered indoor buildings, IFC Section 1007.1.1 Exception 2 reduces this minimum separation to one-third (1/3) of the diagonal.

How is aggregate exit width calculated per occupant?

Under IFC Section 1005.3.2, multiply the governing occupant load by 0.2 inches per occupant for unsprinklered spaces and tents, or 0.15 inches per occupant for sprinklered indoor assembly spaces. For tents, total provided width must also meet the table minimum (required exit count multiplied by minimum width per exit).

When does the 50% main entrance/exit rule apply?

Under IFC Section 1030.2 (1029.2 in earlier editions), indoor Group A assembly occupancies with an occupant load greater than 300 must provide a main entrance/exit capable of accommodating at least 50 percent of the total occupant load.