Tent & Event Exit Count, Width & Separation Calculator
Calculate required exit count, minimum clear doorway width, aggregate exit width, and remote exit separation under IFC Table 3103.11, Section 1005.3.2, and Section 1007.1.1.
Structure & Egress Inputs
Required Egress Schedule
2021 International Fire Code (IFC) | IFC 2021 Table 3103.12.2IFC Table 3103.11 Exit Count & Minimum Width Reference
Active occupant load bracket is highlighted. Tent minimums reflect IFC Table 3103.11 (Table 3103.12.2 in 2018/2021 IFC); indoor minimums reflect IFC Section 1006.2.1 and 1006.3.3.
| Occupant Load | Tent Min Exits | Tent Min Width Each | Tent Min Aggregate | Indoor Min Exits | Indoor Min Door Width |
|---|---|---|---|---|---|
| 10 to 199 | 2 | 72" (6 ft) | 144" | 2 | 36" |
| 200 to 499 | 3 | 72" (6 ft) | 216" | 2 | 36" |
| 500 to 999 | 4 | 96" (8 ft) | 384" | 3 | 36" |
| 1,000 to 1,999 | 5 | 120" (10 ft) | 600" | 4 | 36" |
| 2,000 to 2,999 | 6 | 120" (10 ft) | 720" | 4 | 36" |
| 3,000 or more | 7 | 120" (10 ft) | 840" | 4 | 36" |
Save Plan & Permit Rule Updates
Copy a read-only review link to share with venues or clients now, or save your email for local AHJ permit rule updates.
Frequently Asked Questions
How many exits does an event tent require under IFC Table 3103.11?
IFC Table 3103.11 (Table 3103.12.2 in IFC 2018 and 2021) requires 2 exits of at least 72 inches each for 10 to 199 occupants, 3 exits of 72 inches for 200 to 499 occupants, 4 exits of 96 inches for 500 to 999 occupants, 5 exits of 120 inches for 1,000 to 1,999 occupants, 6 exits for 2,000 to 2,999, and 7 exits for 3,000 or more occupants.
What is the IFC Section 1007.1.1 half-diagonal remote exit rule?
When two or more exits are required, at least two exits must be placed a distance apart equal to not less than one-half (1/2) of the length of the maximum overall diagonal dimension of the room or tent. In fully sprinklered indoor buildings, IFC Section 1007.1.1 Exception 2 reduces this minimum separation to one-third (1/3) of the diagonal.
How is aggregate exit width calculated per occupant?
Under IFC Section 1005.3.2, multiply the governing occupant load by 0.2 inches per occupant for unsprinklered spaces and tents, or 0.15 inches per occupant for sprinklered indoor assembly spaces. For tents, total provided width must also meet the table minimum (required exit count multiplied by minimum width per exit).
When does the 50% main entrance/exit rule apply?
Under IFC Section 1030.2 (1029.2 in earlier editions), indoor Group A assembly occupancies with an occupant load greater than 300 must provide a main entrance/exit capable of accommodating at least 50 percent of the total occupant load.