Space & Code Parameters

Calculated Egress Requirements

2021 International Fire Code (IFC)
PERMIT TRIGGERED
Enclosed tent is 2,400 sq ft (exceeds 400 sq ft fire permit threshold).
Exact IFC Occupant Load Formula (IFC 2021 Table 1004.5)
Net Area = 2,400 gross - 200 stage/bar - 256 dance = 1,944 sq ft
Load = ceil(1,944 / 15) + ceil(256 / 5) = 130 + 52 = 182 occupants
Governing Occupant Load 182 persons (15 sq ft/occ net)
Required Exit Count 2 exits Minimum remote openings
Min Width per Exit 72" Clear unobstructed opening
Aggregate Exit Width 144" 0.2" per occupant factor
Remote Exit Separation 36.1 ft 1/2 diagonal (72.1 ft diag)
Max Travel Distance 100 ft Any point to nearest exit
ADA Wheelchair Spaces 5 spaces IBC Table 1109.2.2.1 (36" x 48")
Illuminated Exit Signs Required Battery backup at 50+ occupants
Open Scaled Floor Plan With These Exact Dimensions

Save Plan & Permit Rule Updates

Copy a read-only review link to share with venues or clients now, or save your email for local AHJ permit rule updates.

Frequently Asked Questions

How is assembly occupant load calculated under IFC Table 1004.5?

Divide net assembly floor area by 15 sq ft/person for unconcentrated tables and chairs, 7 sq ft/person for concentrated chairs without tables, or 5 sq ft/person for standing space and dance floors. Always round up to the next whole person.

How do tent exit widths differ from indoor ballroom doors?

Under IFC Table 3103.11 / 3103.12.2, tents require a minimum clear opening of 72 inches per exit (96 inches at 500 to 999 occupants, 120 inches at 1,000+), whereas indoor assembly doors start at 36 inches minimum width with aggregate width sized at 0.2 inches per occupant (0.15 inches if sprinklered).

What is the remote exit separation rule?

Under IFC Section 1007.1.1, when two exits are required they must be separated by at least half (1/2) the length of the maximum overall diagonal of the room or tent. In sprinklered indoor buildings, this reduces to one-third (1/3) of the diagonal.

How many ADA wheelchair spaces are required for an event?

IBC Table 1109.2.2.1 requires 1 wheelchair space for 4 to 25 seats, 2 for 26 to 50, 4 for 51 to 150, 5 for 151 to 300, and 6 for 301 to 500 seats, each measuring at least 36 inches by 48 inches clear.