Event & Tent Fire Extinguisher Placement Calculator
Verify minimum 2A:10BC extinguisher count, perimeter wall coordinates, 75-foot maximum travel coverage rings, Class K cooking rules, and generator setbacks under NFPA 10 and IFC Section 3104.12.
Footprint & Hazard Parameters
NFPA 10 Coverage & Equipment Schedule
IFC Section 3104.12 & NFPA 10 Table 6.2.1.1NFPA 10 & IFC Fire Extinguisher Reference
| Hazard / Area | Minimum Rating / Spec | Travel / Clearance Rule | Code Citation |
|---|---|---|---|
| General Event / Tent (Class A & B) | 2A:10BC (5 lb or 10 lb dry chemical) | 75 ft max travel distance | IFC 3104.12 / NFPA 10 Table 6.2.1.1 |
| Commercial Cooking / Fryers / Grills | Class K wet chemical | 30 ft max travel distance | IFC 906.4 / NFPA 10 Section 6.6 |
| Portable Generator / Fuel Storage | 2A:10BC (20 ft exterior setback) | 30 ft from generator | IFC 3107.16 / NFPA 10 |
| Mounting Height (Units <= 40 lb) | Top handle <= 5 ft (60 in) above floor | Bottom >= 4 in above floor | NFPA 10 Section 6.1.3.8 |
Annual Inspection Tag & Day-of-Event Checklist
- Current annual licensed service tag punched with month and year (NFPA 10 Section 7.3).
- Pressure gauge needle resting cleanly inside the green operable range.
- Pull pin and tamper seal intact with unobstructed discharge hose and nozzle.
- Mounted on approved bracket or stand with handle no higher than 60 inches and base at least 4 inches off the floor.
- Unobstructed line-of-sight access along exit paths with visible red signage above the unit.
Save Plan & Permit Rule Updates
Copy a read-only review link to share with venues or clients now, or save your email for local AHJ permit rule updates.
Frequently Asked Questions
How many fire extinguishers are required inside an event tent?
Under IFC Section 3104.12 and NFPA 10, portable fire extinguishers rated at least 2A:10BC must be placed so the maximum travel distance from any point inside the tent to the nearest extinguisher does not exceed 75 feet. Most tents up to 40x60 ft can be covered by 1 well-placed unit, while longer tents (40x100 ft and up) require 2 or more units near opposite exits.
When is a Class K fire extinguisher required at an event?
Whenever cooking appliances using combustible vegetable or animal oils and fats (deep fryers, griddles, woks, or open-flame catering stations) are present, IFC Section 906.4 and NFPA 10 Section 6.6 require a listed Class K wet-chemical extinguisher within 30 feet of travel distance.
What is the NFPA 10 mounting height rule for portable extinguishers?
For fire extinguishers weighing 40 pounds or less (including standard 5 lb and 10 lb 2A:10BC units), NFPA 10 Section 6.1.3.8 requires the top of the extinguisher to be mounted no more than 5 feet (60 inches) above the floor, with at least 4 inches of clearance between the bottom of the unit and the floor.
How far must a portable generator be placed from an event tent?
IFC Section 3107.16 requires internal combustion power sources and generators to be isolated from contact with the public by fencing or enclosure and separated at least 20 feet from tents and membrane structures, with a dedicated 2A:10BC extinguisher staged nearby.