Compliant Architectural Schematic (40' x 20')

Scale ref: 1/8" = 1'-0" | Governing Load: 54 occ | Status: FAIL
8/9 CHECKS PASS
40'-0"20'-0"T1T2T3FEEX-1 (72")EX-2 (72")
Egress Exit & Worst-Case Path (28.0 ft / 100 ft max) 2A:10BC Extinguisher (75 ft radius) 60" Round Table (8 seats, 11.5 ft OC)
Banquet (60" Rounds)
24 seats
3 tables at 8 guests each (15 sq ft net)
Ceremony / Theater Chairs
97 seats
IFC Table 1004.5 concentrated chairs (7 sq ft net)
Standing Cocktail
144 guests
IFC Table 1004.5 standing space (5 sq ft net)

IFC Exit & Fire Safety Requirements Table

RequirementCode ReferenceMinimum RequiredThis Layout
Governing Occupant LoadIFC 2021 Table 1004.515 sq ft / person54 occupants
Minimum Number of ExitsIFC Table 3103.112 remote exits2 exits placed
Minimum Width per ExitIFC Table 3103.1172" clear144" total provided
Maximum Egress Travel DistanceIFC 3103.12.1<= 100 ft28.0 ft worst-case
2A:10BC Fire ExtinguishersIFC 3107.9 / NFPA 1075 ft max travel1 unit(s)
ADA Wheelchair SpacesIBC Table 1109.2.2.14 spaces36" x 48" clear floor area each

Fire Permit Triggers by City

Exceeds both standard IFC 400 sq ft enclosed and 700 sq ft open canopy fire permit thresholds.

Ready to add your stage, bar, dance floor, and title block?

Open this exact 20' × 40' Tent footprint in the interactive EgressCAD studio to place tables, verify aisles, and export a scaled Fire Marshal PDF and DXF.

Customize This 20' × 40' Tent & Export Fire Marshal PDF

Frequently Asked Questions

How many people fit in a 20' × 40' Tent?

A 20' × 40' Tent (800 sq ft) holds 24 seated banquet guests at 3 standard 60-inch round tables with compliant 36-inch aisles, up to 97 theater/ceremony chairs (7 sq ft/person), or up to 144 standing cocktail guests (5 sq ft/person).

How many exits are required for a 20' × 40' Tent?

Based on a governing occupant load of 54 under 2021 International Fire Code (IFC), a 20' × 40' Tent requires at least 2 remote exits with a minimum clear opening of 72 inches each.

Does a 20' × 40' Tent require a fire permit?

Exceeds both standard IFC 400 sq ft enclosed and 700 sq ft open canopy fire permit thresholds.

How many fire extinguishers are needed in a 20' × 40' Tent?

At least 1 Class 2A:10BC fire extinguisher(s) placed so that maximum travel distance from any point on the floor does not exceed 75 feet (IFC Section 3107.9 / NFPA 10).